Experiments were conducted to study the effects of enhanced surfaces on heat transfer during spray cooling. The surface enhancements consisted of cubic pin fins, pyramids, and straight fins (uniform cross sectional straight fins) machined on the top surface of copper heater blocks. Each had a cross-sectional area of 2.0 cm~2. Measurements were also obtained on a heater block with a flat surface for baseline comparison purposes. A 2x2 nozzle array was used with PF-5060 as the working fluid. Thermal performance data was obtained under nominally degassed (chamber pressure of 41.4 kPa) and gassy conditions (chamber with N_2 gas at 101 kPa). The results show that the straight fins had the largest enhancement in heat flux. Critical heat flux (CHF) for this surface showed an increase of 55% in comparison to the flat surface for the nominally degassed condition. The cubic pin finned and pyramid surfaces provided slightly more than half the heat flux enhancement (30% - 40% greater than the flat surface) of the straight fins. The gassy case showed that the straight fins again provided the largest enhancement (48%) in CHF relative to the flat surface. This was followed by the cubic pin fins, and pyramids which had increases of 31% and 18% respectively. No significant effect was observed in the surface temperature at which CHF occurs for either portion of the study.
机译:进行实验以研究增强表面在喷雾冷却过程中对热传递的影响。表面增强包括在铜制加热块顶面上加工的立方针状翅片,棱锥和直翅片(均等截面直翅片)。每个具有2.0cm 2的横截面积。还可以在具有平坦表面的加热块上进行测量,以进行基线比较。 2x2喷嘴阵列与PF-5060一起用作工作流体。在标称脱气(腔室压力为41.4 kPa)和气体条件下(腔室中N_2气体为101 kPa)获得热性能数据。结果表明,直翅片的热通量增加最大。该表面的临界热通量(CHF)与标称脱气条件下的平坦表面相比增加了55%。立方针状翅片和金字塔形表面提供的直通散热片的热通量增加量略多于一半(比平坦表面大30%-40%)。高气的情况表明,相对于平坦表面,直翅片再次提供了最大的CHF增强(48%)。其次是立方钉状鳍片和金字塔形,分别增加了31%和18%。在研究的任何一部分中,在发生CHF的表面温度上均未观察到明显影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号