摘要

This paper deals with single phasernferroresonance in high voltage substations withrninductive voltage transformers (VT) and provides anrnoverview of uncritical and critical networkrnconfigurations, parameters influencing thernferroresonance behaviour and measures to avoidrnferroresonance occurrence. A special measure to avoidrnferroresonance, which is applied by Trench Germanyrn(TG), is discussed. This measure is to de-tune the nonlinearrnresonant circuit by a VT iron-core with anrnintegrated air-gap. By means of TG’s VT-design it isrnpossible to avoid ferroresonance occurrence for nearlyrnall substation arrangements. A comparison ofrntheoretically and experimentally obtainedrnferroresonance studies is discussed.
机译:本文研究了带有感应式电压互感器(VT)的高压变电站的单相铁磁谐振,并提供了对非关键和关键网络配置,影响铁磁谐振行为的参数以及避免铁磁谐振发生的措施的概述。讨论了Trench Germanyrn(TG)所采用的一种特殊措施,以防止出现错误纠错。该措施是通过带有未集成气隙的VT铁芯来失谐非线性谐振电路。借助TG的VT设计,几乎可以避免几乎所有变电站布置发生铁磁谐振。讨论了理论上和实验上获得的铁磁共振研究的比较。