APPLICATION OF ON-LINE VERSUS OFF-LINE PD TESTING FOR STATOR INSULATION MONITORING

机译:在线与离线PD测试在定子绝缘监测中的应用

获取原文
获取原文并翻译 | 示例

摘要

Partial discharge testing can effectively diagnose insulation problems in the stator winding of high-voltage generators and motors, since partial discharges are a symptom of the most insulation failure mechanisms. Partial discharge testing can be performed either when the machine is not operating (offline) or during normal machine operation (on-line). Off-line PD testing is a well-known method to assess the stator winding insulation. Over last ten years, on-line PD testing has proven to be a successful technique of monitoring stator insulation condition to forewarn plant personnel of possible machine failures and to help them implement a predictive maintenance program. This paper presents an on-line and off-line PD test on a hydro-generator using the same test instrument and sensors. A comparison of the two tests indicates that the off-line test results are consistent with the on-line test results. Similarities and differences of the on-line and off-line PD tests are discussed.