Risk Based Approach to Substation Earthing for SA Power Networks

机译:SA电网基于风险的变电站接地方法

获取原文

摘要

SA Power Networks has recently adopted the changes to earthing philosophy detailed in EG-0 Power System Earthing Guide. This method determines the risk of fatality for the most exposed individual based on substation fault level, protection clearing times, fault frequency, and human contact to conductive structures. This is currently done using a fault frequency based on standard values given in EG-0. This paper investigates the methods that SA Power Networks use to record interruptions, and how this information can be used to determine an observed earth fault frequency for use in touch voltage threshold calculations. The last 10 years of fault data for a sample of 39 substations was examined and negligible risk touch voltage thresholds were calculated using clearing times of 0.2 seconds and 1.0 seconds. These thresholds were then compared to those determined using the calculated fault frequency based on line length, and using the IEEE 80 deterministic method previously used by SA Power Networks.
机译:SA Power Networks最近采用了EG-0电力系统接地指南中详细介绍的接地原理更改。该方法根据变电站的故障级别,保护清除时间,故障频率以及人与导电结构的接触来确定最暴露的个人的死亡风险。目前,这是根据EG-0中给出的标准值使用故障频率来完成的。本文研究了SA Power Networks用来记录中断的方法,以及如何将此信息用于确定观察到的接地故障频率,以用于触摸电压阈值计算。检查了39个变电站样本的最近10年故障数据,并使用0.2秒和1.0秒的清除时间计算了可忽略的风险接触电压阈值。然后将这些阈值与使用根据线路长度计算出的故障频率并使用SA Power Networks先前使用的IEEE 80确定性方法确定的阈值进行比较。