【24h】

Analysis on Human Adaptive Levels in Different Kinds of Indoor Thermal Environment

机译:不同室内热环境下人的适应水平分析

获取原文
获取原文并翻译 | 示例

摘要

To reveal the law of human adaptive level changing along with indoor temperature and humidity in naturally ventilated buildings,an approach of field survey of thermal comfort has been carried out in an university of Guangzhou for about a year,and adaptive coefficient(λ) proposed in adaptive PMV model (aPMV) has been used to calculate the level of adaptation in different combination of indoor temperature and humidity.The results show that,the effects of different combinations of indoor temperature and humidity on human adaptive level vary from each other obviously,the level of adaptation in cool and dry environment (CDE) and comfortable environment (CE,PMV<O) was low,but it is high in hot and humid environment (HHE) and CE (PMV>O).The adaptive coefficient (λ) are 0.64 (HHE),-0.06(CE,PMV<O),1.07(CE,PMV>O) and -0.37 (CHE),respectively.
机译:为了揭示自然通风建筑中人体适应水平随室内温度和湿度变化的规律,在广州大学进行了大约一年的热舒适度现场调查,并提出了适应系数(λ)。自适应PMV模型(aPMV)已被用于计算不同室内温度和湿度组合的适应水平。结果表明,室内温度和湿度的不同组合对人体适应水平的影响明显不同,阴凉干燥环境(CDE)和舒适环境(CE,PMV <O)的适应水平较低,而在湿热环境(HHE)和CE(PMV> O)较高。分别为0.64(HHE),-0.06(CE,PMV <O),1.07(CE,PMV> O)和-0.37(CHE)。