【24h】

Real Operation Pattern of District Heating System and Its Heating Effects

机译:区域供热系统的实际运行模式及其热效应

获取原文
获取原文并翻译 | 示例

摘要

A field study has been carried out for one district heating system in Beijing. According to the surveyed data, operation pattern of the district heating system has been discussed and quantitative relationship between supply water temperatures with outdoor temperatures has been developed. It indicates a fine linear correlation of daily temperature of supply water with weighted outdoor temperature within three days and an operation condition of "large flow rate and small temperature difference". Additionally, the effects of the operation pattern on energy consumption and indoor air temperature have been presented. Results show that the heat supply of this heating system couldn't meet the exact requirements for different rooms and at different time, and failed to build a stable indoor thermal environment in terms of space and time.
机译:对北京的一个区域供热系统进行了现场研究。根据调查数据,讨论了区域供热系统的运行模式,并开发了供水温度与室外温度之间的定量关系。它表示三天内供水的日温度与加权室外温度和“大流量,小温差”的运行条件之间的良好线性关系。另外,已经提出了操作模式对能量消耗和室内空气温度的影响。结果表明,该供暖系统的供热不能满足不同房间,不同时间的确切需求,无法在空间和时间上建立稳定的室内热环境。