In chamber experiments, we investigated the effectiveness of a task ventilation system with an air supply nozzle located underneath the front edge of a desk and directing air toward a heated mannequin seated at the desk. The task ventilation system provided outside air, while another ventilation system provided additional space cooling but no outside air. Test variables included the vertical angle of air supply (-15°to 45°from horizontal), and the supply flow rate of (3,5 to 6.5 L s~(-1)). Using the tracer gas step-up and step-down procedures, the measured air change effectiveness (i.e., exhaust air age divided by age of air at the mannequin's face) ranged from 1.4 to 2.7, which is higher than typically reported for commercially available task ventilation or displacement ventilation systems.
机译:在室内实验中,我们研究了任务通风系统的有效性,该任务通风系统的空气供应喷嘴位于桌子的前边缘下方,并将空气引向坐在桌子上的加热的人体模型。任务通风系统提供外部空气,而另一个通风系统提供额外的空间冷却,但没有外部空气。测试变量包括空气供应的垂直角度(与水平方向成-15°至45°),以及供应流量(3.5至6.5 L s〜(-1))。使用示踪气体升压和降压程序,测得的换气效率(即,排气年龄除以人体模特面部的空气年龄)在1.4到2.7之间,高于通常报告的市售任务通风或置换通风系统。