首页> 外文会议>The 6th Asian conference on refrigeration and air conditioning-towards the sustainable development >EXPERIMENTAL INVESTIGATION OF A HIGH-TEMPERATURE AIR-SOURCE HEAT PUMP WATER HEATER
【24h】

EXPERIMENTAL INVESTIGATION OF A HIGH-TEMPERATURE AIR-SOURCE HEAT PUMP WATER HEATER

机译:高温空气源热泵热水器的实验研究

获取原文
获取原文并翻译 | 示例

摘要

This work experimentally investigates the impact of several operating parameters on the heating performance of a high-temperature air-source heat pump water heater.The operating parameters considered in the study are the air inlet temperature,hot water inlet temperature,flow rate of hot water,while the heating performance studied here include the heating capacity of the condenser,power consumption of the compressor,and COP of the heat pump.The effect of temperature lift of heat pump on COP is also discussed.The results show that the temperature lift of heat pump could be served as an indicator for the assessment of COP.The COP will decrease by 15.8% for each 10K increment of temperature lift for the moderate-temperature air-source heat pump.The COP is 2.1,when the temperature lift of the heat pump is 75.1℃ and the supply temperature of hot water is 85℃.
机译:这项工作通过实验研究了几个工作参数对高温空气源热泵热水器的加热性能的影响。研究中考虑的工作参数是进气温度,热水入口温度,热水流量。在此研究的热性能包括冷凝器的热容量,压缩机的功耗和热泵的COP。还讨论了热泵的温度升高对COP的影响。结果表明,热泵的温度升高热泵可以作为评估COP的指标。对于中温空气源热泵,每升高10K升温,COP就会降低15.8%。COP值为2.1时,热泵为75.1℃,热水供应温度为85℃。

著录项

  • 来源
  • 会议地点 Xian(CN)
  • 作者

    LEE T.S; Huang W.C;

  • 作者单位

    Department of Energy and Refrigerating Air-Conditioning Engineering,National Taipei University of Technology,No.1,Sec.3,Chung-Hsiao E.Rd.,Taipei,10608,Taiwan;

    Department of Energy and Refrigerating Air-Conditioning Engineering,National Taipei University of Technology,No.1,Sec.3,Chung-Hsiao E.Rd.,Taipei,10608,Taiwan;

  • 会议组织
  • 原文格式 PDF
  • 正文语种 eng