首页> 外文会议>4th International Conference on Sustainable Energy Technologies >A Test of Harnessing Roofwater for Non-potable Uses at a Residential District in Hangzhou
【24h】

A Test of Harnessing Roofwater for Non-potable Uses at a Residential District in Hangzhou

机译:杭州某居民区非饮用水用屋顶水治理试验

获取原文
获取原文并翻译 | 示例

摘要

Water demands are constantly increasing in HangZhou because of industrial development and increasing population. Hence, there is a continuous search for new sources and one such source is roofwater from high-rise buildings. In this paper the experiment of collecting the roofwater from the south spine of a residential district in HangZhou was done and utilising it for non-potable uses was discussed, too. A well-established simple input—output model incorporating a dual-mode system (DMS) of operation has been used so as to ensure that all the collected roofwater from an area of 18,75 m~2 is used only for non-potable purposes. The design parameters were optimized leading to a rainwater storage tank linked to the existing water tanks with pump cut-in and cut-out electrodes placed at depths of 1 and 1.5 m above the base of the tank that will ensure that the supply of water will always be available for the non-potable uses.
机译:由于工业发展和人口增加,杭州的需水量不断增加。因此,人们一直在寻找新的水源,其中一个水源是高层建筑的屋顶水。本文完成了从杭州某居民区南脊收集屋顶水并将其用于非饮用水的实验。已经使用了建立良好的简单输入输出模型,该模型结合了双模式操作系统(DMS),以确保从18,75 m〜2区域收集的所有屋顶水仅用于非饮用水用途。优化设计参数,将雨水储罐连接到现有的水罐,并在水罐底部上方1和1.5 m的深度处将泵的切入和切出电极放置在泵中,以确保供水始终可用于非饮用水用途。