THD improvement of phase voltages via injection of voltage in neutral conductor for three phase four wire distribution system

机译:通过向三相四线配电系统中性导体注入电压来改善相电压

获取原文
获取原文并翻译 | 示例

摘要

The effect of non-linear and unbalanced loads on the three phase four wire transformers are discussed in this paper. Unbalanced systems and harmonic load causes harmonic current to flow through the neutral wire of the distribution transformer and hence decreases the transformer utilization factor and efficiency of the system. Increase in the amount of neutral current causes over burden of the neutral wire and increase losses. Nowadays series active power filters are widely used to mitigate the effect of harmonics and in the case of three phase transformer, three separate active filters are required to reduce the total harmonic distortion of each conductor. In this research only one active power filter is installed in the return path of neutral wire of three phase four wire system. Simulations carried out show that only placing a single filter in neutral path, the THD of phase conductor voltages is much improved. Matlab/Simulink platform is chosen to perform simulation and the results are discussed for non linear and unbalanced loads.
机译:本文讨论了非线性和不平衡负载对三相四线变压器的影响。系统不平衡和谐波负载会导致谐波电流流经配电变压器的中性线,从而降低变压器的利用率和系统效率。中性线电流量的增加会导致中性线的负担过重并增加损耗。如今,串联有源电力滤波器被广泛用于减轻谐波的影响,对于三相变压器,需要三个独立的有源滤波器来减少每个导体的总谐波失真。在这项研究中,三相四线制系统的中性线返回路径中仅安装了一个有源功率滤波器。进行的仿真表明,仅在中性路径中放置一个滤波器,相导体电压的THD就会大大提高。选择Matlab / Simulink平台进行仿真,并讨论了非线性和不平衡负载的结果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号