首页> 外文会议>2017 International Conference on High Voltage Engineering and Power Systems >Condition assessment model for GIS operating under tropical conditions
【24h】

Condition assessment model for GIS operating under tropical conditions

机译:热带条件下运行的GIS条件评估模型

获取原文
获取原文并翻译 | 示例

摘要

Gas Insulated Switchgear (GIS) has been in use in transmission system for more than 30 years with good reliability. However, in our case study of 631 CB-bays of GIS operating under tropical conditions, we observed failure rates over twice the value reported in the 3rd CIGRE's survey of 2007. Following this observation, it becomes practically important to develop a condition assessment model for GIS operating under tropical conditions. As a part of this process, knowledge rules for humidity content in SF6 insulation were investigated through the experiment inside the HV Laboratory in TU Delft with a solid-and-gas insulation setup with AC voltage stress. The controlled parameter used in the experiments were resembling the actual condition in tropics. In this paper, the condition assessment model for GIS is proposed. To support the model, different diagnostics to assess the critical components of GIS operating under tropical conditions are discussed. Following that, an example of knowledge rules to interpret the outcome from the diagnostics is also given.
机译:气体绝缘开关设备(GIS)在传输系统中已经使用了30多年,并且具有良好的可靠性。但是,以我们在热带条件下运行的631个CB湾的案例研究为例,我们观察到的故障率是2007年第三届CIGRE调查报告的两倍。为热带条件下运行的GIS开发条件评估模型非常重要。作为此过程的一部分,通过在代尔夫特州TU高压实验室内使用带有AC电压应力的固体和气体绝缘设置,研究了SF 6 绝缘中湿度含量的知识规则。实验中使用的控制参数与热带地区的实际情况相似。本文提出了GIS的状态评估模型。为了支持该模型,讨论了评估热带条件下运行的GIS关键组件的不同诊断方法。随后,还给出了一个知识规则的示例,以解释诊断结果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号