首页> 外文会议>2017 IEEE Manchester PowerTech >Risk of cable overheating and premature ageing due to load control measures
【24h】

Risk of cable overheating and premature ageing due to load control measures

机译:负载控制措施会导致电缆过热和过早老化的风险

获取原文
获取原文并翻译 | 示例

摘要

Cyclic ratings are dependent on the load curve present on an underground cable. If the load curve changes the cable rating must be adjusted or the operator risks overheating and damaging the cable. Many have suggested using demand response or energy storage to allow networks to remain within ratings during contingencies. Unfortunately the resulting load profiles could cause the real circuit ratings to be lower than expected. This paper will show that without updating ratings to allow for manipulated load curves network operators risk overheating and damaging cables if demand response is used on a network. However, a case study shows that the demand response required to cause overheating incidents is very significant and may not occur in reality.
机译:循环额定值取决于地下电缆上的负载曲线。如果负载曲线发生变化,则必须调整电缆额定值,否则操作员可能会面临过热和损坏电缆的危险。许多人建议使用需求响应或能量存储来使网络在突发事件期间保持在额定范围内。不幸的是,所得的负载曲线可能导致实际电路额定值低于预期。本文将显示,如果在网络上使用需求响应,则不更新额定值以允许操纵负载曲线,网络运营商就有过热和损坏电缆的风险。但是,案例研究表明,导致过热事件所需的需求响应非常重要,实际上可能不会发生。