首页> 外文会议>2017 IEEE Manchester PowerTech >Influence of fault-ride-through requirements for distributed generators on the protection coordination of an actual distribution system with reclosers
【24h】

Influence of fault-ride-through requirements for distributed generators on the protection coordination of an actual distribution system with reclosers

机译:分布式发电机故障穿越要求对带重合闸的实际配电系统保护协调的影响

获取原文
获取原文并翻译 | 示例

摘要

This paper analyses the existing protection scheme of a real distribution system with distributed generators, in Greece. Network protection utilizes three successive reclosers at the main trunk and fuses at the laterals. The generating units are protected by overcurrent and voltage/frequency relays. The analysis focuses on the fault-ride-through capability of the generating units and proposes the resetting of the generators and network protection relays so as to conform to the requirements imposed by distribution system operators and international standards. The proposed protection system guarantees selectivity for any short-circuits occurring inside or outside the distribution system, irrelative if the generating units are connected to the network or not. Meaningful conclusions are derived from the application of the proposed protection coordination principle.
机译:本文分析了希腊具有分布式发电机的实际配电系统的现有保护方案。网络保护在主干处使用三个连续的重合器,在分支处使用熔断器。发电机组受过电流和电压/频率继电器的保护。分析着重于发电机组的故障排除能力,并提出了发电机和网络保护继电器的复位方法,以符合配电系统运营商和国际标准的要求。所提出的保护系统可保证对配电系统内部或外部发生的任何短路的选择性,而与发电机组是否已连接到网络无关。从提出的保护协调原则的应用中得出有意义的结论。

著录项

  • 来源
  • 会议地点 Manchester(GB)
  • 作者单位

    Dept. of Electrical and Computer Engineering, Democritus University of Thrace, Xanthi, Greece;

    Dept. of Electrical and Computer Engineering, Democritus University of Thrace, Xanthi, Greece;

    Dept. of Electrical and Computer Engineering, Democritus University of Thrace, Xanthi, Greece;

    Dept. of Automatic Control and Systems Engineering, The University of Sheffield, Sheffield, UK;

    Dept. of Automatic Control and Systems Engineering, The University of Sheffield, Sheffield, UK;

  • 会议组织
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Relays; Fuses; Generators; Delay effects; Standards; Guidelines; Solids;

    机译:继电器;保险丝;发电机;延迟效应;标准;准则;固体;
  • 入库时间 2022-08-26 13:54:46