首页> 外文会议>2017 IEEE Manchester PowerTech >Implementation and validation of the Nordic test system in DIgSILENT PowerFactory
【24h】

Implementation and validation of the Nordic test system in DIgSILENT PowerFactory

机译:在DIgSILENT PowerFactory中实施和验证北欧测试系统

获取原文
获取原文并翻译 | 示例

摘要

This paper presents the implementation of the Nordic test system in DIgSILENT PowerFactory. The implemented system is a variant of the Nordic32 network and is based on the technical report “Test Systems for Voltage Stability Analysis and Security Assessment” prepared by the IEEE Power System Dynamic Performance Committee, the Power System Stability Subcommittee, and the Test Systems for Voltage Stability and Security Assessment Task Force. This work deems all of the implemented controllers and validates the PowerFactory implementation against the original model presented in the aforementioned technical report. It is shown through RMS simulations that the action of load tap changers and over excitation limiters are leading forces through a long-term voltage collapse and therefore, their accurate modeling is crucial. Furthermore, the implemented system can be whether downloaded from the IEEE PES Power System Dynamic Performance Committee website or requested directly to the authors.
机译:本文介绍了DIgSILENT PowerFactory中北欧测试系统的实现。实施的系统是Nordic32网络的变体,其基于IEEE电力系统动态性能委员会,电力系统稳定性小组委员会和电压测试系统编写的技术报告“用于电压稳定性分析和安全评估的测试系统”稳定与安全评估工作队。这项工作认为所有已实现的控制器均已实现,并根据上述技术报告中提出的原始模型验证了PowerFactory的实现。通过RMS仿真显示,负载分接开关和过励磁限制器的作用是通过长期电压崩溃的主导力量,因此,它们的精确建模至关重要。此外,既可以从IEEE PES动力系统动态性能委员会网站上下载实现的系统,也可以直接向作者索取。