Pre-determination of partial discharge inception voltage in power cables using electrode gaps in air under AC voltage

机译:使用交流电压下空气中的电极间隙预先确定电力电缆中的局部放电起始电压

获取原文
获取原文并翻译 | 示例

摘要

The breakdown of insulation in cables while in service can cause considerable damage to equipment and the accessories to which they are connected. PD in cables arises due to the overstressing of cable insulation resulting from electric field enhancement caused by imperfections in cable core and screen. The nature and magnitude of PD activity depends upon the type of defect, aging, environmental factors, applied voltage and cable loading. Reduction in system voltage can potentially reduce PD, which will correspondingly extend the service life of the cable. Currently, industry voltage statutory requirements permit ±6% tolerance setting on nominal voltage on distribution networks. This ±6% voltage reduction on may have little or an adverse effect on PD magnitude depending on the nature of defect present in the cable. Hence there is a clear requirement to pre-determine the PD inception voltage in cables through laboratory experiments to understand the significance of voltage reduction. This means to verify the effect of voltage reduction on extinguishing or minimizing PD activity in cables. In this paper, range of voltages at which PD incepts termed as partial discharge inception voltage(PDIV) is measured using a test cell containing different types of electrode configuration having different spacing. PDIV measured using the test cell is verified by conducting partial discharge testing in paper insulated lead covered (PILC) and cross-linked poly ethylene(XLPE) cables. It has been found that PDIV measured using the test cell and cable are in good agreement.
机译:使用中电缆绝缘层的破坏会严重损坏设备及其连接的附件。电缆中的PD是由于电缆芯线和屏蔽层的缺陷引起的电场增强而导致电缆绝缘层承受的应力过大。 PD活动的性质和大小取决于缺陷的类型,老化,环境因素,施加的电压和电缆负载。降低系统电压可能会降低PD,从而相应地延长电缆的使用寿命。当前,工业电压法规要求允许在配电网络的标称电压上设置±6%的容差。根据电缆中存在的缺陷的性质,这种±6%的电压降低可能对PD幅度影响很小或不利。因此,明确需要通过实验室实验来预先确定电缆中的PD起始电压,以了解降压的重要性。这意味着要验证电压降低对电缆中PD活动的抑制或最小化的影响。在本文中,使用包含不同类型,间距不同的电极配置的测试电池,测量PD称为局部放电起始电压(PDIV)的电压范围。通过在纸绝缘铅皮(PILC)和交联聚乙烯(XLPE)电缆中进行局部放电测试,验证了使用测试电池测得的PDIV。已经发现,使用测试单元和电缆测得的PDIV非常吻合。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号