首页> 外文会议>2016 IEEE Smart Energy Grid Engineering >Direct control method for a PV system integrated in an Indirect Matrix Converter-based UPQC
【24h】

Direct control method for a PV system integrated in an Indirect Matrix Converter-based UPQC

机译:集成在基于间接矩阵转换器的UPQC中的光伏系统的直接控制方法

获取原文
获取原文并翻译 | 示例

摘要

This paper proposes a direct control method for a three-phase Photovoltaic (PV) system integrated on the Low-Voltage grid, using an Indirect Matrix Converter (IMC)-based Unified Power Quality Conditioner topology. This topology adds enhanced Power Quality functionality to the PV inverter when connected to a sensitive non-linear load, such as load current harmonics mitigation and voltage sags, swells and harmonics compensation. The PV array is inserted in the DC link of the IMC, which is controlled with a direct sliding mode control method. This direct control allows using a specific modulation method for the shunt converter that guarantees the DC link voltage is adequate for the operation of the IMC. Simulation results are presented to confirm the proper operation of the system under a variety of operating conditions.
机译:本文提出了一种基于基于间接矩阵转换器(IMC)的统一电能质量调节器拓扑结构的低压电网上集成的三相光伏(PV)系统的直接控制方法。当连接到敏感的非线性负载时,此拓扑为PV逆变器增加了增强的电能质量功能,例如负载电流谐波缓解和电压骤降,骤升和谐波补偿。 PV阵列插入到IMC的DC链路中,该IMC通过直接滑模控制方法进行控制。这种直接控制允许对分流转换器使用特定的调制方法,以确保DC链路电压足以满足IMC的操作。给出了仿真结果,以确认系统在各种运行条件下的正常运行。