首页> 外文会议>2016 IEEE International Conference on Power System Technology >Calculation method for harmonic impedance of traction substation grounding grid
【24h】

Calculation method for harmonic impedance of traction substation grounding grid

机译:牵引变电所接地网谐波阻抗的计算方法

获取原文
获取原文并翻译 | 示例

摘要

Due to the high harmonic content in the traction return current, it is inappropriate to calculate the rail potential and other parameters by grounding impendence of traction substation under power frequency, and it is necessary to take harmonic grounding impendence into consideration. The effect of the harmonic grounding return current on the grounding grid is studied, and a calculation method for the harmonic impedance of the traction substation grounding grid is proposed based on the combination of field measurement and simulation. In the method, an equivalent model of grounding grid is established by software SIMULINK and the model parameters are calculated on the basis of the power frequency grounding impendence. It is found that harmonic current not only affects grounding impedance, but also leads to the increase of the surface potential, and the potential distribution is not uniform. The proposed method is verified by the comparison with software CDEGS.
机译:由于牵引返回电流中谐波含量较高,因此不宜通过工频下牵引变电站的接地阻抗来计算轨道电势和其他参数,因此必须考虑谐波接地阻抗。研究了谐波接地回路电流对接地网的影响,并结合实测与仿真,提出了牵引变电站接地网谐波阻抗的计算方法。该方法通过SIMULINK软件建立等效的接地网模型,并根据工频接地阻抗计算模型参数。发现谐波电流不仅会影响接地阻抗,还会导致表面电势的增大,且电势分布不均匀。通过与软件CDEGS的比较验证了所提出的方法。