The operation of modern power electronic switches located in photovoltaic (PV) inverters have the potential to create high frequency harmonic (HFH) distortions. This paper investigates the emission of such distortions by PV inverters installed in a Brazilian solar farm. High-resolution measurements are performed on three different commercial inverters, with 15 kVA rated capacity each. Results obtained from the specific measurements presented in this paper reveal HFH current distortions may reach up to 2% of fundamental frequency current, whereas HFH voltages remain below 0.2% of fundamental frequency voltage. Therefore, results suggest HFH distortions emitted by these specific PV inverters are unlikely to cause significant problems to the utility.
机译:位于光伏(PV)逆变器中的现代电力电子开关的运行可能会产生高频谐波(HFH)失真。本文研究了安装在巴西太阳能发电站中的光伏逆变器产生的此类畸变。高分辨率测量在三个不同的商用逆变器上进行,每个逆变器的额定容量为15 kVA。从本文介绍的特定测量中获得的结果表明,HFH电流畸变可能达到基频电流的2%,而HFH电压仍低于基频电压的0.2%。因此,结果表明,这些特定的PV逆变器发出的HFH失真不太可能对公用事业造成严重问题。