IMPINGEMENT COOLING IN A SIMULATED DATA CENTER SERVERS WITH AN ARRAY OF ELLIPTIC AIR JETS

机译:具有椭圆形空气射流阵列的模拟数据中心服务器中的冲击冷却

获取原文
获取原文并翻译 | 示例

摘要

Reducing the electricity consumption from the cooling systems in a data center can cut the energy cost. The development of the high efficiency cooling schemes can effectively save more energy from the computer room air conditioning (CRAC) system. Impingement cooling with air jets can achieve high heat transfer rates and could be used to cool local hot spots in the cabinets. A 5 × 5 jet array was designed utilizing circular and elliptic holes. The cross sectional area of the test region was 250 mm × 25 mm. The jet Reynolds numbers is 3300. Heat transfer coefficients on the target surface were investigated. Results indicated that the impingement cooling provided lower surface temperature than the traditional fan cooling.
机译:减少数据中心冷却系统的电力消耗可以降低能源成本。高效冷却方案的开发可以有效地从计算机机房空调(CRAC)系统中节省更多能量。空气射流的冲击冷却可以实现较高的热传递率,并可用于冷却机柜中的局部热点。利用圆形和椭圆形孔设计了一个5×5的射流阵列。测试区域的横截面积为250mm×25mm。雷诺数为3300。研究了目标表面的传热系数。结果表明,冲击冷却提供的表面温度低于传统风扇冷却。