首页> 外文会议>2014 International Conference on Power System Technology: Towards Green, Efficient and Smart Power System >Research on live working of tower with V-type insulator extending to tower body for ±800kV UHVDC transmission line
【24h】

Research on live working of tower with V-type insulator extending to tower body for ±800kV UHVDC transmission line

机译:±800kV特高压直流输电线路带V型绝缘子伸入塔架的塔架带电工作研究

获取原文

摘要

For the specific 4 towers with V-type insulator extending to tower body for Hami-Zhengzhou ± 800kV UHVDC transmission project, live working security analysis is carried out, the required minimum safe distance and the minimum combined gap distance under various working conditions are calculated, which determines the way to getting in and out of the equipotential of the tower with V-type insulator extending to tower body, in addition, the safety distance is also checked under the condition of different working locations, according to the checked results, appropriate measures are proposed to take when the air gap distance does not meet the risk rate requirement, which makes a great significance for the operation, maintenance and spreading of tower with V-type insulator extending to tower body.
机译:对于具有V型绝缘体的特定4个塔,延伸到哈比郑州±800kV UHVDC传输项目的塔架,进行了现场工作安全分析,计算了所需的最低安全距离和各种工作条件下的最小组合间隙距离,这决定了使用延伸到塔架的V型绝缘体进出塔的等电位的方式,此外,根据所检查的结果,在不同工作位置的情况下还检查安全距离,适当的措施建议在空气隙距离不符合风险率要求时,这对塔架延伸到塔体的V型绝缘体具有重要意义,维护和扩散。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号