Lightning caused outages in the Austrian Power Grid transmission line network

机译:雷电造成奥地利电网传输线网络中断

获取原文
获取原文并翻译 | 示例

摘要

Austria is one of the European countries with relatively high lightning activity [1] and lightning is a main cause of transmission line outages. In this presentation we have analyzed in detail lightning caused outages in the grid of the Austrian transmission system operator Austrian Power Grid (APG). 222 outage related lightning flashes were identified in the database of the Austrian lightning location system ALDIS as these flashes were located within a corridor of ±1 km along the considered lines and within a time window of ±1 second of the recorded outage time. These 222 flashes (203 of negative and 19 of positive polarity) are analyzed in terms of their local occurrence along the transmission lines and their peak currents. Tower footing resistances, which are affecting the occurrence of back flashover failures, were found to be log-normal distributed with a median of 4.4 Ω and a σ = 1.1. Median peak current of negative and positive flashes causing transmission line outages is -11.3 kA and 37.9 kA, respectively, and median distance of flash locations to the line is 322 m.
机译:奥地利是雷电活跃程度较高的欧洲国家之一[1],雷电是造成输电线路中断的主要原因。在本演示中,我们详细分析了奥地利输电系统运营商奥地利电网(APG)的电网中的雷电造成的停电。在奥地利闪电定位系统ALDIS的数据库中识别出222次与停电有关的闪电,因为这些闪光灯沿着所考虑的线位于±1 km的走廊内,并且在所记录的停电时间的±1秒的时间范围内。根据在传输线上的局部闪烁及其峰值电流,对这222个闪烁(负极性为203,正极性为19)进行了分析。发现影响后向闪络故障发生的塔架基础电阻为对数正态分布,中位数为4.4Ω,σ= 1.1。导致传输线中断的负向和正向闪光峰值电流的中位数分别为-11.3 kA和37.9 kA,并且闪光位置到传输线的中值距离为322 m。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号