首页> 外文会议>2014 International Conference on High Voltage Engineering and Application >Partial discharge localization on dry-type transformers
【24h】

Partial discharge localization on dry-type transformers

机译:干式变压器的局部放电局部化

获取原文
获取原文并翻译 | 示例

摘要

In this paper an electrical partial discharge (PD) localization technique for a dry type power transformer is presented. The method has been tested in the laboratory on real transformer coil as well as on a transformer in a test bay. Calibration signal is injected through a plate sensor placed along the winding on the surface of the transformer coil in different positions, thus PD signals can be measured at both coil terminal sites using digitizer. Measured PD signal during test can be then evaluate and compared with calculated transfer function. The described technique enables not only localization of the PD source also determination of the apparent charge. This evaluation can be more accurate than conventional PD measurements by use of quadruple and coupling capacitor calibration and can be used during manufacturing process as well as diagnostic in field.
机译:本文提出了一种干式电力变压器的局部放电局部放电技术。该方法已在实验室的真实变压器线圈上以及测试架中的变压器上进行了测试。校准信号是通过板式传感器注入的,该板式传感器沿着变压器线圈表面上不同位置的绕组放置,因此可以使用数字转换器在两个线圈端子位置测量PD信号。然后可以评估测试期间测得的PD信号,并将其与计算的传递函数进行比较。所描述的技术不仅能够实现PD源的定位,还能够确定视在电荷。通过使用四重和耦合电容器校准,该评估可以比传统的PD测量更准确,并且可以在制造过程以及现场诊断中使用。