Application of the integrated AE and HFCT sensors for online Dry-type Transformer Partial Discharge Monitoring. Case study

机译:集成AE和HFCT传感器在线干式变压器局部放电监测中的应用。案例分析

获取原文
获取原文并翻译 | 示例
           

摘要

This study proposes a measurement technique to identify and determine the occurrence of partial discharge in the insulation of Dry-type transformers, as well as their criteria level. Concerning IEC 62478, the four AE (acoustic emission) sensors were used to determine the PD sources and one HFCT (High-Frequency Current Transducer) technique was to identify the PD source and the criteria level. This process accurately identified the PD source location occurring at any position in a transformer. The gap time was 3.2 ms. The level of partial discharge for this case study is Major PD that means soon monitoring every 3 months. The results of this technique could prevent insulation failure of a transformer in time.
机译:该研究提出了一种测量技术来识别和确定干式变压器绝缘中的局部放电的发生,以及它们的标准水平。关于IEC 62478,使用四个AE(声发射)传感器来确定PD源,一个HFCT(高频电流换能器)技术是识别PD源和标准水平。该过程精确地识别在变压器中的任何位置发生的PD源位置。差距时间为3.2毫秒。这种情况研究的部分放电水平是主要的PD,这意味着每3个月内很快监测。该技术的结果可以防止变压器的绝缘失效。