In this Paper,leakage current obtained by laboratory was derived to calculate the pollution flashover voltage of porcelain insulators.On this basis,this Paper analyzed the basic theory of prediction of pollution flashover based on leakage current monitored in service.At the same time,the calculation results and the test results of pollution flashover voltage were compared The results showed that the difference of flashover voltage between calculation results and test results was less than 5%.It is proved that the calculation method for evaluating the flashover risk by monitoring the leakage current proposed in this Paper was effective.
机译:本文推导了实验室获得的泄漏电流,以计算出陶瓷绝缘子的污染闪络电压。在此基础上,本文分析了基于运行中监测的泄漏电流的污染闪络预测的基本理论。将计算结果与污染闪络电压测试结果进行比较,结果表明,计算结果与测试结果之间的闪络电压差小于5%。证明了通过监测漏电流评估闪络风险的计算方法本文提出的建议是有效的。