Accurate power system monitoring plays a vital role in detection of supply problems within the supply grid. Of all parameters being monitored, rms based measurements are used to detect various voltage based events within the system. IEEE and IEC based standards utilize full cycle instantaneous samples repeated every half a cycle for the calculation of rms. These measurements are not without limitations especially for short duration variations. This paper proposes 4-instantaneous sample points sampled at 90 degrees apart (quadrature based rms) to estimate rms and further detect voltage events in real-time. The proposed method is experimentally tested and applied for voltage events monitoring using Labview FPGA CompactRio platform. The results demonstrate the effectiveness of the proposed method for estimating the signal rms value with less number of samples.
机译:准确的电力系统监控在检测电网内部的供电问题中起着至关重要的作用。在所有受监视的参数中,基于均方根的测量值用于检测系统内各种基于电压的事件。基于IEEE和IEC的标准利用每半个周期重复一次的全周期瞬时采样来计算均方根值。这些测量并非没有局限性,尤其是对于短时变化而言。本文提出了以90度间隔采样的四个瞬时采样点(基于正交均方根值),以估计均方根值并进一步实时检测电压事件。该方法经过实验测试,并用于使用Labview FPGA CompactRio平台进行电压事件监控。结果证明了所提出的方法在减少样本数量的情况下估计信号均方根值的有效性。