首页> 外文会议>CIRED 2012;Workshop on Integration of Renewables into the Distribution Grid >Experimental validation of control strategies for a microgrid test facility including a storage system and renewable generation sets
【24h】

Experimental validation of control strategies for a microgrid test facility including a storage system and renewable generation sets

机译:对包含存储系统和可再生发电机组的微电网测试设施的控制策略进行实验验证

获取原文
获取原文并翻译 | 示例

摘要

The paper is aimed at describing and validating some control strategies in the SYSLAB experimental test facility characterized by the presence of a low voltage network with a 15 kW-190 kWh Vanadium Redox Flow battery system and a 11 kW wind turbine. The generation set is connected to the local network and is fully controllable by the SCADA system. The control strategies, implemented on a local pc interfaced to the SCADA, are realized in Matlab-Simulink. The main purpose is to control the charge/discharge action of the storage system in order to present at the point of common coupling the desired power or energy profiles.
机译:本文旨在描述和验证SYSLAB实验测试设施中的一些控制策略,这些控制策略的特征是存在一个低压网络,该低压网络具有15 kW-190 kWh钒氧化还原液流电池系统和11 kW风力涡轮机。发电机组已连接到本地网络,并且可由SCADA系统完全控制。在与SCADA接口的本地PC上实现的控制策略在Matlab-Simulink中实现。主要目的是控制存储系统的充电/放电动作,以便在公共耦合点提供所需的功率或能量分布。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号