Optimal position for driven rod of combined vertical and horizontal grounding electrodes under lightning

机译:雷电作用下垂直和水平组合接地电极从动杆的最佳位置

获取原文
获取原文并翻译 | 示例

摘要

The property of grounding electrodes under lightning is important issue for lightning protection. This paper focuses on the optimal position for driven rod of combined vertical and horizontal grounding electrodes under lightning. The optimal positions where the vertical driven rod is connected to the horizontal electrode with different length are suggested based on field testing and numerical simulation. The results indicate that two factors influence the optimal location together, namely the coupling electromagnetic effect between the grounding conductors, and the effective length of the grounding conductor. As for a cross grounding electrodes, if the horizontal grounding electrode is relatively short the driven rods should be installed at the terminal because the former factor plays the leading role.
机译:接地电极在雷电下的特性是防雷的重要问题。本文着眼于雷电作用下垂直和水平组合接地电极的驱动杆的最佳位置。根据现场试验和数值模拟,提出了垂直驱动杆与不同长度的水平电极连接的最佳位置。结果表明,两个因素共同影响最佳位置,即接地导体之间的耦合电磁效应和接地导体的有效长度。对于交叉接地电极,如果水平接地电极比较短,则从动杆应安装在端子上,因为前者起主导作用。