首页> 外文会议>2012 Fifth International Conference on Intelligent Computation Technology and Automation >Load Characteristics Analysis of the Primary Side of Three Typical Traction Transformers with Various Power Factor Definitions
【24h】

Load Characteristics Analysis of the Primary Side of Three Typical Traction Transformers with Various Power Factor Definitions

机译:三种不同功率因数定义的典型牵引变压器一次侧的负载特性分析

获取原文
获取原文并翻译 | 示例

摘要

Aimed at the nonlinear, asymmetric and fluctuant characteristics of the traction loads, this paper researches and analyzes the loading characteristics and power factor values of V-V, Y-D11 and Impedance-Matching traction transformers by a novel approach. Four definitions of power factor are compared-three considering harmonics and unbalances and one base only on fundamental components. This paper verifies the Impedance-Matching transformer superiority on restraining imbalance from power factor. The simulation results and actual measurement data reveal that, compared with other power factors, according to distort and imbalance, the effective power factor could be recommended for use in fairly evaluating the load characteristics for traction transformers.
机译:针对牵引负载的非线性,不对称和波动特性,采用一种新颖的方法,研究并分析了V-V,Y-D11和阻抗匹配牵引变压器的负载特性和功率因数。比较了功率因数的四种定义,其中三种考虑了谐波和不平衡,一种仅基于基本成分。验证了阻抗匹配变压器在抑制功率因数不平衡方面的优越性。仿真结果和实际测量数据表明,与其他功率因数相比,根据失真和不平衡情况,可以推荐有效功率因数用于公平评估牵引变压器的负载特性。