首页> 外文会议>2012 9th International Symposium on Telecommunications. >Impulse noise influence on communication system in high-voltage substation
【24h】

Impulse noise influence on communication system in high-voltage substation

机译:脉冲噪声对高压变电站通信系统的影响

获取原文
获取原文并翻译 | 示例

摘要

In real high voltage systems, it is necessary to observe system parameters. Depend on investigated values, it is possible to detect malfunctions or overvoltage in high-voltage substation. Because of these, communication system in actual high voltage substation is implemented. In the high-voltage substation disconnector and circuit breaker are installed, whose operation causing appearance of impulse noise effect in the present communication system. Disconnector's contacts in air-insulated substations (AIS) are moving slowly causing numerous strikes and re-strikes between contacts. Every strike causes high-frequency currents (from a few hundred kHz to a few MHz) tending to equalize potentials at the contacts. These processes are the source of impulse noise in the connected communication system. In this paper measured impulse noise level and estimate influence to probability of false alarm appearance in the communication system are presented.
机译:在实际的高压系统中,必须注意系统参数。根据调查的值,可以检测高压变电站中的故障或过电压。因此,在实际的高压变电站中实现了通信系统。在高压变电站中,安装了隔离开关和断路器,它们的操作引起在本通信系统中出现脉冲噪声效应。空气绝缘变电站(AIS)中隔离开关的触头正在缓慢移动,从而导致触头之间发生多次触击和重新触击。每次撞击都会引起高频电流(从几百kHz到几MHz),趋于使触点上的电势相等。这些过程是所连接的通信系统中脉冲噪声的来源。本文介绍了测量的脉冲噪声水平,并估计了对通信系统中虚假警报出现概率的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号