FIRE PROTECTION OF COMPUTER ROOM WITH WATER MIST SYSTEMS

机译:带有水雾系统的计算机房防火

获取原文

摘要

This paper presents an investigation of performance for a combined fire detection and zoned water mist fire suppression system. Full scale tests were conducted to identify the basic design requirements for a multi-zone water mist suppression system to protect a computer room underfloor, individual cabinets and computers, arrays of cable trays in the ceiling plenum. Results show that the high pressure water mist does perform well when applied in a 'total flooding' mode in obstructed compartments. Extinguishment was achieved within one minute. Reignition was well prohibited through cooling effect of water mist. It was also noted that very fine sprays (Dv0.5~100microns) were suitable for live electronic equipment areas, provided better control over spread of humidity in the facility, as well as better penetration of grouped cables.
机译:本文对组合式火灾探测和分区水雾灭火系统的性能进行了研究。进行了全面测试,以确定多区域水雾抑制系统的基本设计要求,该系统可保护地板下的计算机室,单个机柜和计算机,天花板通风室中的电缆桥架阵列。结果表明,当高压水雾以“全淹没”模式应用于受阻隔室时,效果很好。一分钟内达到灭绝。由于水雾的冷却作用,严禁重燃。还应注意的是,非常细的喷雾剂(Dv0.5〜100微米)适用于带电的电子设备区域,可以更好地控制设备中的湿度分布,并更好地渗透成组的电缆。