This paper will cover the case study of a Westinghouse, 496 MVA hydrogen inner-cooled generator stator's core problem. The unit is located at the City Public Service owned JT Deely plant in San Antonio, Texas. Items discussed in this paper include CPS' experience with loose cores, EL CID testing, Loop testing, and concerns with extending intervals between generator inspections. The primary interest of this paper is to discuss the continued operation of a stator core that according to testing criteria should not be capable of operation.
机译:本文将涵盖西屋公司496 MVA氢内冷发电机定子铁心问题的案例研究。该部门位于得克萨斯州圣安东尼奥市政府公共服务拥有的JT迪利工厂。本文讨论的内容包括CPS在松散磁芯方面的经验,EL CID测试,回路测试,以及有关延长发电机检查间隔的担忧。本文的主要目的是讨论定子铁心的持续运行,根据测试标准,该定子铁心不能运行。