首页> 外文会议>The 14th International workshop on atmospheric icing of structures. >DEVELOPMENT OF FLASHOVER VOLTAGE TEST METHOD FOR SNOW ACCRETED INSULATORS-PRELIMINARY TEST WITH 33 KV CLASS INSULATOR SAMPLES -
【24h】

DEVELOPMENT OF FLASHOVER VOLTAGE TEST METHOD FOR SNOW ACCRETED INSULATORS-PRELIMINARY TEST WITH 33 KV CLASS INSULATOR SAMPLES -

机译:积雪式绝缘子闪络电压测试方法的开发-带33 KV绝缘子样品的初步测试-

获取原文
获取原文并翻译 | 示例

摘要

As the preliminary attempt to develop a 154 kV class full-scale snow test procedure to be used for evaluation of various insulator designs, flashover voltage tests of snow accreted insulators were carried out with 33 kV class insulator samples. The test procedure consisted of four steps, 1) generation of artificial snow with defined conductivity, 2) accretion of packed snow on the insulator, 3) increase of liquid water content of the accreted snow, 4) voltage application. The voltage tests showed that the level of flashover voltage was comparable with the service voltage during the Niigata field outage, and the results were also repeatable. The test method was preliminary verified for the full-scale transmission class insulators.
机译:作为开发用于评估各种绝缘子设计的154 kV级满量程雪测试程序的初步尝试,对33 kV类绝缘子样品进行了积雪绝缘子的闪络电压测试。测试程序包括四个步骤:1)产生具有规定电导率的人造雪; 2)在绝缘子上积聚堆积的雪; 3)增加积雪的液态水含量; 4)施加电压。电压测试表明,在新泻田间停电期间,击穿电压的水平与工作电压相当,结果也是可重复的。该测试方法已针对大型传输级绝缘子进行了初步验证。