The doubly-fed induction generator (DFIG) based wind turbines of today are often equipped with a crowbar, which can be used to limit the inrush rotor current and protect the ac excitation converter from damage via a set of resistors that are connected to the rotor windings of the DFIG. When the rotor current becomes too high due to the severe grid voltage dips on the transmission line, the crowbar is activated and the rotor side converter is disconnected from the rotor windings at the same time, which makes the DFIG behave as a squirrel cage induction generator with increased rotor resistance. This paper analyzes the influence of the crowbar resistors on the electrical behavior of the DFIG during the grid voltage dips. Approximate expression of the fault stator and rotor currents are deduced from mathematical analysis and verified by simulation. Different crowbar by-pass resistances and their impacts on the maximal fault currents and electromagnetic torque are examined by simulations with different parameter sets of the DFIG. Based on the simulation results, the appropriate crowbar by-pass resistance can be effectively predicted.
机译:如今,基于双馈感应发电机(DFIG)的风力涡轮机通常配备有撬棍,该撬棍可用于限制浪涌转子电流,并通过与转子相连的一组电阻器来保护交流励磁转换器不受损坏。 DFIG的绕组。当由于传输线上的严重电网电压骤降而使转子电流变得过高时,撬棒被激活,同时转子侧变流器与转子绕组断开连接,这使DFIG表现为鼠笼式感应发电机转子电阻增加。本文分析了在电网电压骤降期间,撬棍电阻对DFIG电气性能的影响。通过数学分析推导出故障定子和转子电流的近似表达式,并通过仿真进行验证。通过使用DFIG的不同参数集进行仿真,研究了不同的撬棍旁路电阻及其对最大故障电流和电磁转矩的影响。根据仿真结果,可以有效地预测适当的撬棍旁路电阻。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号