首页> 外文会议>11th IIR conference on phase-change materials and slurries for refrigeration and air conditioning >PASSIVE COOLING POTENTIAL OF TWO DIFFERENT PCM COOLING CEILINGS IN THE ENERGY EFFICIENCY CENTER
【24h】

PASSIVE COOLING POTENTIAL OF TWO DIFFERENT PCM COOLING CEILINGS IN THE ENERGY EFFICIENCY CENTER

机译:节能中心中两种不同PCM冷却天花板的被动冷却潜势

获取原文
获取原文并翻译 | 示例

摘要

In the Energy Efficiency Center – the new R&D building of the ZAE Bayern - two different PCM cooling ceiling types are installed and monitored in two office rooms. The ceilings are connected to a water circuit and can be used for heating or cooling. The PCM ceilings are prototypes which differ in the positioning of the PCM layer: ceiling type 1 with the PCM on top of and ceiling type 2 with the PCM below the water pipes. It was found, that cooling ceiling type 2 had a better thermal connection between PCM and room, nevertheless, the passive cooling power of the two different system designs was quite similar when measured as a function of the room globe temperature. Passive cooling powers of 10 to 15 W per m² PCM cooling ceiling area were measured for an operative room temperature of 26 °C.
机译:在能源效率中心(ZAE拜仁公司新的研发大楼)中,在两个办公室安装并监视了两种不同的PCM冷却天花板类型。天花板连接到水回路,可用于加热或冷却。 PCM天花板是原型,不同之处在于PCM层的位置:天花板类型1的PCM位于顶部,天花板类型2的PCM位于水管下方。已经发现,2型冷却天花板在PCM和房间之间具有更好的热连接,但是,根据房间地球温度测量,两种不同系统设计的被动冷却功率非常相似。在室温为26°C的情况下,每平方米PCM冷却天花板面积的被动冷却功率为10至15W。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号