首页> 外国专利> Governing system for reheat steam turbine powerplant

Governing system for reheat steam turbine powerplant

机译:再热汽轮机调节系统

摘要

918,779. Steam turbine plant. GENERAL ELECTRIC CO. Aug. 6, 1959 [Aug. 22, 1958], No. 26904/59. Class 110 (3). A steam turbine plant comprising a steam generator feeding a turbine stage which discharges through a reheater and intercept valve to a further turbine stage, has starting valves to admit limited quantities of live steam directly from the steam generator to the inlets of the turbine stages and actuating means for progressively closing the starting valves as the intercept valve opens during starting. The plant shown comprises a super-pressure turbine section 3, the exhaust from which passes through a reheater 43 to a high-pressure turbine section 4. The turbine section 4 discharges through a reheater 42 to two intermediate pressure sections 4, 5 arranged in parallel which discharge through low-pressure turbine sections 7, 8 to condensers. The turbine sections 3, 5, 7 form a first turbine unit 1 and the sections 4, 6, 8 a second turbine unit 2. Steam is fed to the turbines from a boiler 44 and superheater 47. Valves 13, 14, 15 are intercept valves arranged to shut off steam to the turbine sections 4, 5 and 6, respectively, in an emergency. The plant is started as follows. When the steam generator and turbine are cold, the boiler feed pump 45 is started up and circulates cold water through the boiler 44, superheater 47, super high pressure turbine by-pass valve 50, conduit 51, water separator 52, and condenser hot well 54. When 30% of the rated flow is established, the boiler is fired and the water pressure rises to the full rated pressure. The by-pass 50 is controlled by the pressure and temperature at the superheater outlet. As the temperature rises a certain amount of the water flashes into steam as it passes through the valve 50. The water is separated from the mixture in the separator 52 and returned to the condenser hot-well 54. The steam passes through conduits 55, 56, highpressure reheater 43 and conduit 57 to the high-pressure turbine by-pass valve 58 and then through conduit 50 to the low-pressure reheater 42. This reheater discharges through a lowpressure turbine by-pass valve 61 to the condenser 62. As the heat input to the boiler 44 increases, water is injected into the desuperheating spray chambers 63, 64, 65 to prevent damage to the piping and condenser tubes. During this process the by-pass valves 58 and 61 are adjusted manually so as to gradually raise the pressures maintained in the high and lowpressure reheaters 43, 42. To warm up the turbine sections 3, 4, a small amount of warming steam is admitted to the discharge ends of these turbines by manually opening the valves 66, 67. After warming, the valves 66, 67 are manually closed and the boiler stop valve 70, main stop valve 48, high-pressure reheater stop valve 72 and the low-pressure reheater stop valves 73, 74 manually opened. The adjustable loadlimiting device 35 is now backed away from the right hand end of lever 20 which rises and causes rack 25 to rotate cams 75, 79, 77, and open the pilot valve 10 in the main control valve 9 and two starting valves 11, 12. This admits live steam into the turbine sections 3, 4, 5 and through conduit 38 to the turbine section 6. Orifices 39, 40, 78 limit the flow. The quantity of steam is so selected that the heat generated in the respective turbine sections by turbulence is removed. When the governor 28 reaches the rated speed the generator driven by the turbine is connected to an A.C. network so that when the synchronizing device 29 is actuated to open the valves 11, 12, 13 any tendency for the turbine to overspeed is prevented. This action continues until the cam-shaft 16 fully opens the starting valves 10, 11, 12. At this point the cam 76 begins to open the intercept valve 14, cam 21 the intercept valve 13 and cam 22 the intercept valve 15. At the same time as valves 13, 14, 15 begin to open, the valve actuating rod 36 begins to lift the main governor valve 37. Further actuation of the synchronizing device 29, begins to close the starting valves 11, 12 and to open the intercept valves 13, 14, 15. This operation continues until the valves 11, 12 are completely closed and the valves 13, 14, 15 fully open. This is the normal operating condition. During starting the by-pass valve 50 has been acting to maintain the discharge pressure at the superheater outlet. By the time 30% load is reached by-pass valve 50 is completely closed. Under these conditions, the by-pass valves 58 and 61 are completely closed. All the boiler flow is now passing through the main inlet valve to the turbine 3 and through the intercept valves 13, 14, 15 to the turbines 4, 5, 6. The intercept valves 13, 15 are actuated by the main governor 28 acting through links 30, 31, 32. The valves 13, 15 may also be operated by the pre-emergency governor 34 if the speed for which the governor is set is exceeded.
机译:918,779。蒸汽轮机厂。通用电气公司,1959年8月6日[Aug. [1958年2月22日],第26904/59号。 110级(3)。一种蒸汽轮机设备,其包括蒸汽发生器,该蒸汽发生器向涡轮机级馈送,该涡轮机级通过再热器和截流阀排放到另一个涡轮机级,该涡轮机具有启动阀,以将有限量的新鲜蒸汽直接从蒸汽发生器进入涡轮机级的入口并进行致动。用于在截流阀在起动过程中打开时逐步关闭起动阀的装置。所示的设备包括超压涡轮机部分3,废气从中通过再热器43到达高压涡轮机部分4。涡轮机部分4通过再热器42排放到两个平行布置的中压部分4、5。其通过低压涡轮部分7、8排放到冷凝器。涡轮部分3、5、7形成第一涡轮单元1,而部分4、6、8形成第二涡轮单元2。蒸汽从锅炉44和过热器47供给到涡轮。阀13、14、15被截断。紧急情况下,分别关闭蒸汽至涡轮机部分4、5和6的阀门。该工厂如下启动。当蒸汽发生器和涡轮机变冷时,锅炉给水泵45启动,并使冷水循环通过锅炉44,过热器47,超高压涡轮机旁通阀50,导管51,水分离器52和冷凝器热井。 54.当达到额定流量的30%时,将燃烧锅炉,并且水压将升至最大额定压力。旁路50由过热器出口处的压力和温度控制。随着温度升高,一定量的水在通过阀50时会闪蒸成蒸汽。水在分离器52中与混合物分离并返回冷凝器热井54。蒸汽通过导管55、56 ,高压再热器43和导管57到达高压涡轮旁通阀58,然后通过导管50到达低压再热器42。该再热器通过低压涡轮旁通阀61排放到冷凝器62。输入到锅炉44的热量增加,水被注入到减温喷雾室63、64、65中,以防止损坏管道和冷凝器管。在该过程中,手动调节旁通阀58和61,以逐渐升高维持在高压和低压再热器43、42中的压力。为了预热涡轮机部分3、4,允许少量的预热蒸汽通过手动打开阀门66、67,将其连接到这些涡轮机的排放端。加温后,手动关闭阀门66、67,并关闭锅炉截止阀70,主截止阀48,高压再热器截止阀72和低压手动打开压力再热器截止阀73、74。现在,可调节的负载限制装置35背离杠杆20的右端,后者上升并导致齿条25旋转凸轮75、79、77,并打开主控制阀9中的先导阀10和两个启动阀11, 12.这允许新鲜蒸汽进入涡轮机部分3、4、5,并通过导管38进入涡轮机部分6。孔口39、40、78限制了流量。选择蒸汽量以消除在各个涡轮部分中由于湍流产生的热量。当调速器28达到额定转速时,由涡轮机驱动的发电机被连接到交流网络,从而当致动同步装置29以打开阀11、12、13时,防止了涡轮机超速的任何趋势。该动作一直持续到凸轮轴16完全打开启动阀10、11、12为止。此时,凸轮76开始打开拦截阀14,凸轮21拦截阀13和凸轮22拦截阀15。在阀13、14、15开始打开的同时,阀致动杆36开始抬起主调速阀37。同步装置29的进一步致动,开始关闭启动阀11、12并打开截止阀13、14、15继续该操作,直到阀11、12完全关闭并且阀13、14、15完全打开。这是正常的工作条件。在启动期间,旁通阀50已经起作用以维持过热器出口处的排出压力。到达到30%的负载时,旁通阀50完全关闭。在这些条件下,旁通阀58和61完全关闭。现在,所有锅炉流都通过主进气阀到达涡轮机3,并通过截流阀13、14、15到达涡轮机4、5、6。截流阀13、15由主调速器28驱动,通过如果超出了调速器的设定速度,则阀13、15也可以由应急前调速器34操作。

著录项

  • 公开/公告号US2902831A

    专利类型

  • 公开/公告日1959-09-08

    原文格式PDF

  • 申请/专利权人 GENERAL ELECTRIC COMPANY;

    申请/专利号US19580756607

  • 发明设计人 CLARK GORDON W.;IPSEN PETER G.;

    申请日1958-08-22

  • 分类号F01K3/22;F01K7/24;

  • 国家 US

  • 入库时间 2022-08-23 19:39:42

相似文献

  • 专利
  • 外文文献
  • 中文文献
获取专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号