Comparison of Field Measurements and EMT Simulation Results on a Multi-Level STATCOM for Grid Integration of London Array Wind Power Plant

机译:用于伦敦阵列风力发电厂电网整合的多级sTaTCOm的现场测量和EmT仿真结果比较

摘要

Simulation results are widely used in the design of electrical systems such as offshore wind power plants (OWPPs) and for determination of grid compliance. Measurements constitute an important part in the evaluation process of the OWPP, including passive and active components such as the static compensator (STATCOM). Quality measurement data allow the system designer to obtain real-life knowledge on the operating characteristics of the electrical component(s) for various operating scenarios of both the OWPP and the external grid. Furthermore, measurement data constitute an indispensable part of the evaluation of the simulation models of the OWPP components.The purpose of this paper is to develop and validate an electromagnetic transient (EMT) generic model of the modular multi-level cascaded converter (MMCC) STATCOM based on comparison with field measurements. For this purpose, measurement data have been acquired on a commercial ±50 MVAr state-of-the-art (SOA) MMCC STATCOM. The STATCOM is located at the point of common connection (PCC) at the world’s largest OWPP, London Array (LAOWPP). According to the authors’ knowledge, the presented paper will be the first of its kind to compare a detailed model of the STATCOM with actual field measurements for a commercial MMCC STATCOM.Furthermore, the paper offers the reader, being a researcher, transmission system operator, converter designer or a WPP developer etc., the unique opportunity to gain in-depth knowledge of the operating characteristics of the STATCOM for wind power integration, as well as of the validity of applying a generic model of the STATCOM without knowledge of the actual implemented control system.The proposed model is integrated into an aggregated EMT model of LAOWPP, which will be used to investigate possible resonance phenomena that will be shown in the paper to affect the harmonic distortion level. The STATCOM distortion level will be shown to be highly affected by the number of wind turbine generators (WTGs) in service. It will be shown that the inclusion of band rejection filters (BRFs) in the WTGs’ control loop lowers the STATCOM distortion level. It is found that the total inter-harmonic distortion (TIHD) index calculated according to IEC Standard 61000-4-7 is useful for assessing possible and undesired control interaction between the power electronic devices (PEDs) in OWPPs. The total harmonic distortion (THD) index, on the other hand, is found to contain very little information on possible PED controller interaction.
机译:仿真结果被广泛用于电气系统的设计中,例如海上风力发电厂(OWPPs)以及确定电网的合规性。测量是OWPP评估过程中的重要组成部分,包括无源和有源组件,例如静态补偿器(STATCOM)。质量测量数据允许系统设计人员获得有关OWPP和外部电网的各种运行方案的电气组件运行特性的真实知识。此外,测量数据构成了OWPP组件仿真模​​型评估中必不可少的部分。本文的目的是开发和验证模块化多级级联转换器(STATCC)STATCOM的电磁瞬变(EMT)通用模型基于与实地测量的比较。为此,已经在商用±50 MVAr最新技术(SOA)MMCC STATCOM上获取了测量数据。 STATCOM位于全球最大的OWPP伦敦阵列(LAOWPP)的公共连接点(PCC)。根据作者的知识,本文将是第一个将STATCOM的详细模型与商用MMCC STATCOM的实际现场测量进行比较的论文,此外,本文还为读者提供了研究人员和传输系统运营商的职责,转换器设计人员或WPP开发人员等,这是获得深入了解STATCOM进行风电集成的运行特性以及在不了解实际情况的情况下应用STATCOM通用模型的有效性的独特机会所提出的模型被集成到LAOWPP的EMT聚合模型中,该模型将用于研究可能的共振现象,该现象将在本文中显示出来,以影响谐波失真水平。 STATCOM失真水平将显示受使用中的风力涡轮发电机(WTG)数量的严重影响。结果表明,在WTG的控制环路中包含带阻滤波器(BRF)可以降低STATCOM失真水平。发现根据IEC标准61000-4-7计算的总谐波间失真(TIHD)指数可用于评估OWPP中的功率电子设备(PED)之间可能的和不希望的控制相互作用。另一方面,发现总谐波失真(THD)指标几乎没有关于可能的PED控制器相互作用的信息。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号