首页> 外文OA文献 >Beoordeling van foutstroombijdragestrategieën door vermogenelektronische gedistribueerde bronnen
【2h】

Beoordeling van foutstroombijdragestrategieën door vermogenelektronische gedistribueerde bronnen

机译:通过电力电子分布式电源评估故障电流贡献策略

摘要

It is a clear trend that the share of Distributed Generation (DG) in the grid increases. Many DG units are Converter Based DG (CBDG) units and it is expected that the number of CBDG units will increase in the future. Due to the variable nature of most of these CBDG units, there will be occasions when the share of CBDG units is much higher than their average share in the energy production. During these periods, several of the conventional synchronous generators will be disconnected from the grid and scenarios with a large number of CBDG units and very few synchronous generators arise.The goal of this dissertation is to evaluate the impact of these scenarios on the fault currents and voltages during balanced and unbalanced faults. On the one hand, fault currents have a direct impact on the protection system of the grid. On the other hand, the grid voltages during a fault determine the impact of the fault on the loads and the generation units. Therefore, both the fault currents and fault voltages strongly influence the reliability of the grid.First, it is demonstrated that existing control systems of CBDG units are able to flexibly control the fault current injections of CBDG units. Thus, their fault behaviour is a design parameter. Several specific control aspects related to the injection of negative sequence currents during faults are explained.Since detailed electromagnetic transient simulations are considered computationally too intensive for scenarios with multiple CBDG units, this dissertation investigates which simplified method is able to evaluate the fault currents and fault voltages in these scenarios. As the fault behaviour of CBDG units is a design parameter, it is clear that any method has to take into account the control objectives of the CBDG units. Based on these requirements, a simplified calculation framework is developed and validated. This framework is then used to evaluate different current contribution strategies during balanced and unbalanced faults in scenarios with a high share of CBDG.For balanced faults, the influence of different voltage support settings on the short-circuit power in the grid is investigated. It is shown that CBDG units, with the appropriate voltage support settings, can contribute to the short-circuit power of the grid. This way, the CBDG units limit the drop in short-circuit power at the higher voltage levels when they replace conventional generation. When this reduction of the short-circuit power at the higher voltage levels is limited, the fault currents at the lower voltage levels, supplied by the higher voltage levels, do not change significantly. This avoids a complete redesign of the existing protection systems of typical European medium and low voltage grids in scenarios with a high share of CBDG and little conventional generation, as these protection systems rely on the magnitude of the fault currents. Locally, the voltage support of CBDG units can result in a (limited) increase of the short-circuit power. The voltage support can then be applied until the short-circuit power limits of the local grid are reached.For unbalanced faults, scenarios with a high share of CBDG and little conventional generation are evaluated. When only positive sequence voltage support is applied, and negative sequence currents are blocked by the CBDG units, this can lead to very low fault currents during unbalanced faults. These low fault currents would require a complete redesign, including huge investment costs, of the existing protection systems at the lower voltage levels of the grid, as these protection systems rely on the magnitude of the fault currents. In addition, very low fault currents result in a reduced reliability of the grid, as faults at lower voltage levels then have a significant impact on the higher voltage levels. The remaining synchronous generators in the grid also experience additional stress when CBDG units only provide positive sequence voltage support during unbalanced faults. When CBDG units provide both positive and negative sequence voltage support, these drawbacks are avoided: the existing protection systems of typical European medium and low voltage grids do not require a complete redesign, faults on the lower voltage levels do not have a significant impact on the higher voltage levels and the remaining synchronous generators don't experience additional stress.
机译:一个明显的趋势是,分布式发电(DG)在电网中的份额增加了。许多DG单元是基于转换器的DG(CBDG)单元,预计将来CBDG单元的数量会增加。由于大多数这些CBDG装置的可变性,有时CBDG装置的份额要比其在能源生产中的平均份额高得多。在此期间,一些常规的同步发电机将与电网断开连接,并且出现大量CBDG单元的情况,并且出现的同步发电机很少。本文的目的是评估这些情况对故障电流和故障电流的影响。平衡和不平衡故障期间的电压。一方面,故障电流直接影响电网的保护系统。另一方面,故障期间的电网电压确定故障对负载和发电单元的影响。因此,故障电流和故障电压都强烈影响电网的可靠性。首先,证明了现有的CBDG单元控制系统能够灵活地控制CBDG单元的故障电流注入。因此,它们的故障行为是设计参数。解释了与故障期间注入负序电流有关的几个具体控制方面。由于对于具有多个CBDG单元的场景,详细的电磁暂态仿真被认为在计算上过于密集,因此本文研究了哪种简化方法能够评估故障电流和故障电压在这些情况下。由于CBDG单元的故障行为是设计参数,因此很明显,任何方法都必须考虑CBDG单元的控制目标。基于这些要求,开发并验证了简化的计算框架。然后,该框架用于评估在CBDG份额较高的情况下在平衡和不平衡故障期间的不同电流贡献策略。对于平衡故障,研究了不同电压支持设置对电网短路功率的影响。结果表明,具有适当电压支持设置的CBDG单元可导致电网短路功率。这样,当CBDG单元替代常规发电单元时,它们会限制较高电压下的短路功率下降。当限制在较高电压电平下的短路功率的减小时,由较高电压电平提供的较低电压电平的故障电流不会显着变化。这避免了在CBDG份额很高且常规发电量很少的情况下,对典型的欧洲中低压电网现有保护系统的完整重新设计,因为这些保护系统依赖于故障电流的大小。在本地,CBDG单元的电压支持会导致(有限)短路功率增加。然后可以施加电压支持,直到达到本地电网的短路功率极限为止。对于不平衡故障,将评估CBDG份额高且常规发电量少的情况。如果仅施加正序电压支持,而负序电流被CBDG单元阻塞,则在不平衡故障期间可能导致极低的故障电流。这些低故障电流将需要对电网处于较低电压水平的现有保护系统进行全面的重新设计,包括巨额投资成本,因为这些保护系统依赖于故障电流的大小。此外,极低的故障电流会降低电网的可靠性,因为较低电压水平的故障会严重影响较高电压水平。当CBDG单元仅在不平衡故障期间提供正序电压支持时,电网中其余的同步发电机也会承受额外的压力。当CBDG单元同时提供正序和负序电压支持时,可以避免以下缺点:典型的欧洲中,低压电网的现有保护系统不需要完全重新设计,较低电压水平的故障不会对电网造成重大影响。较高的电压水平,其余的同步发电机不会承受额外的压力。

著录项

  • 作者

    Wijnhoven Thomas;

  • 作者单位
  • 年度 2015
  • 总页数
  • 原文格式 PDF
  • 正文语种 en
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号