Health Hazard Evaluation Report HETA 91-257-2184, Ohio Civil Rights Commission, 200 Goodall Complex, Cincinnati, Ohio.

机译:健康危害评估报告HETa 91-257-2184,Ohio Civil Rights Commission,200 Goodall Complex,Cincinnati,Ohio。

获取原文

摘要

In response to an employer request, an investigation was undertaken of poor indoor air quality at the Ohio Civil Rights Commission (SIC-9441), Cincinnati, Ohio. The Commission occupied three floors of an office building which was newly renovated in 1985. Complaints began following water leaks from condensate pans in the air handling units on third floor east and third floor west beginning in August of 1990. Carbon-dioxide (124389) concentrations, temperature and relative humidity were measured during the study at six different locations inside the building. Carbon-dioxide levels rose from a mean of 366 parts per million (ppm) in the morning to a mean of 638ppm in the afternoon. Temperatures ranged from 69.9 to 75.3 degrees-F. Relative humidity ranged from 51.5 to 75.5%. Over half the employees had experienced symptoms such as nasal congestion, headaches, or eye irritation while in the building. The filters for the outside air supply fit poorly and allowed dust from the outside to go around the filters, permitting entrance of organic material into the air handling system. Significant moisture blowby of the cooling coils was also noted. According to the authors, there was no clear evidence that the employees' respiratory symptoms were caused by contaminants in the building; however, the presence of thermophilic actinomycetes within the building raises concern. The authors recommend specific measures to help reduce complaints related to the indoor climate of the building.

著录项

相似文献

  • 外文文献
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号