首页> 美国政府科技报告 >Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
【24h】

Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

机译:在高环境温度下运行的R22和R410a空调器的比较

获取原文

摘要

R22 and R410A split air-conditioning systems were tested and compared as outdoor temperature ranged from 27.8 DGC (82.0 DGF) to 54.4 DGF (130 DGF) The R410A system tests were extended to 68.3 DGC (155.0 DGF) ambient temperature with a customized compressor. Capacity and efficiency of both systems decreased linearly with increasing outdoor temperature, but the R410A system performance degraded more than the R22 system performance. Operation of the R410A system was stable during all tests, including those with the customized compressor extending up to the 68.3 DGF (155.0 DGF) outdoor temperature and resulting in a supercritical condition at the condenser inlet. No noticeable changes in noise level or operation of the system was noted.