Testing of Indoor Radon Reduction Techniques in Central Ohio Houses: Phase 2 (Winter 1988-1989)

机译:俄亥俄州中部房屋室内氡减少技术测试:第2阶段(1988-1989冬季)

获取原文

摘要

The report gives results of tests of developmental indoor radon reduction techniques in nine slab-on-grade and four crawl-space houses near Dayton, Ohio. The slab-on-grade tests indicated that, when there is a good layer of aggregate under the slab, the sub-slab ventilation (SSV) mitigation technique, with only one or two suction pipes, can generally reduce indoor concentrations below 2 pCi/L (86 to 99% reduction). These reductions can be achieved even when: there are forced-air supply ducts under the slab; the slab is large (up to 2600 sq ft); and the foundation walls are hollow block. Operating the SSV system in suction always gave greater reductions than did operating in pressure. The crawl-space tests demonstrated that depressurizing under a plastic liner over the crawl-space floor was able to reduce living-area radon concentrations below 2 pCi/L (81 to 96% reduction). The performance of such sub-liner depressurization gave better reductions than did crawl-space ventilation (blowing air into, or out of, the crawl space). Completely covering the crawl-space floor with plastic sheeting was not always necessary to get adequate performance.