首页> 美国政府科技报告 >Fire Tests in Ventilated RoomsnExtinguishment of Fire in Grouped Cable Trays
【24h】

Fire Tests in Ventilated RoomsnExtinguishment of Fire in Grouped Cable Trays

机译:通风房间的防火测试在分组电缆桥架中灭火

获取原文

摘要

The purpose of the work was to determine the required automatic sprinkler design density necessary to extinguish a developing fire in a grouped cable tray instal¬lation. Four preliminary tests and four extinguishment tests using PE/PVC cable were conducted within a specially designed, ventilated room. The results showed that an average design density of approximately 0.20 mm/s (0.30 gpm/ft2) discharged from automatic sprinklers with a 13-mm (1/2-in.) orifice, 71℃ (160℉) temperature rating and 3.05-m x 3.05-m (10-ft x 10-ft) spacing provided successful extinguish¬ment for the specific grouped cable tray fires investigated. The results also pro¬vided data on a case where a developing fire in a grouped cable tray installation did not open any of the installed standard sensitivity sprinklers, suggesting an¬other parameter (i.e., higher sensitivity sprinklers) in need of attention.