Frequency Control Characteristics of a Direct-Mode Untreated Sewage Source Heat Pump in the Heating Mode

机译:一种直流式未经处理的污水源热泵在加热模式下的变频控制特性

获取原文
获取原文并翻译 | 示例

摘要

An untreated sewage source heat pump system directly makes use of the urban raw sewage instead of that treated by a sewage plant. At present In China, most systems adopt the indirect mode for avoiding the harmful effect of the sewage on the heat pump unit. In this article a direct-mode untreated sewage source heat pump system, which shows less theoretical analysis of the mathematical model, is theoretically designed and analyzed to simulate the system dynamic characteristics in the heating mode. The results show that the system COP changes from 4.1 to 3.4 and the heating capacity from 9.5 to 15.3 kW when the sewage inlet temperature is 12°C and the frequency increases from 18 to 32 HZ. The condenser heat-transfer coefficient increases with the frequency reducing while the change trend of evaporator heat-transfer coefficient is the opposite. The highest values of them are 303 and 1617 W.m~(-2)·K~(-1), respectively. The frequency control simulation supplies the operation adjustment with theoretical instructions and some reference values.
机译:未经处理的污水源热泵系统直接利用城市原污水,而不是污水厂处理的污水。目前,我国大多数系统采用间接方式,避免污水对热泵机组的有害影响。本文设计并分析了一种对数学模型进行较少理论分析的直接模式未处理污水源热泵系统,以模拟供热模式下的系统动态特性。结果表明:当进污温度为12°C,频率由18 HZ增加到32 HZ时,系统COP由4.1变为3.4,制热能力从9.5 kW变为15.3 kW;冷凝器传热系数随频率降低而增大,而蒸发器传热系数的变化趋势则相反。其中最高值分别为303和1617 W.m~(-2)·K~(-1)。变频调速仿真为运行调整提供理论说明和一些参考值。

著录项

获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号