Tightening requirements on industrial boilers and furnaces will require hands-free techniques to (1) assure peak performance wilh respeci to emission, and (2) assure an ability to achieve peak performance throughout a load duty cycle. In the present paper, robust optimal control of a model industrial, swirl-stabilized, natural gas-fired burner is explored as a strategy to attain and maintain low flue-gas nitrogen oxide concentration (NOxconcomitant with high combustion efficiency (#x3B7;c). A performance index, J, is defined such that the maximization of J correlates to optimal burner performance, with respect to NOxand #x3B7;c. Two parameters, swirl intensity (S#x2019;) and excess air (EA), are made amenable to control and incorporated as variable burner inputs. For a given load, the settings of EA and S'are automatically adjusted by a specialized search algorithm in order to maximize the performance index, thereby optimizing #x3B7;xand NOx. The robustness of the approach is demonstrated and evaluated by initiating a change in load and observing the reaction of the modified control system. The control scheme is shown to effectively increase and maintain overall burner performance. Implementation of robust optimal control to practical systems is discussed in terms of challenges outstanding and opportunities to integrate with overall system performance.
展开▼