首页> 外文期刊>IEEE Transactions on Power Electronics >Impedance-Based Aggregation of Paralleled Power Factor Correction Converters in Data Centers
【24h】

Impedance-Based Aggregation of Paralleled Power Factor Correction Converters in Data Centers

机译:Impedance-Based Aggregation of Paralleled Power Factor Correction Converters in Data Centers

获取原文
获取原文并翻译 | 示例
       

摘要

Existing aggregation methods for large-scale data center power systems often overlook disparities in power supply units, leading to reduced accuracy in the small signal dynamics of aggregated model. To fill this gap, this article develops an impedance-based aggregation method for paralleled power factor correction (PFC) converters with heterogeneities in power levels, conduction modes, and line impedances. The closed-loop input admittances of PFC converters operating in continuous conduction mode (CCM) and discontinuous conduction mode (DCM) are presented first. The parametric scaling is then derived to aggregate multiple PFC converters at different power levels and operation modes, including the CCM, DCM, and mixed conduction mode, at the rack level. Furthermore, the aggregation rule and criteria for paralleled PFC converters with unequal line impedances is developed to provide a reduced-order dynamic model for adjacent server racks. The proposed parameter scaling and aggregation method allow efficient interaction analysis and stability assessment for data center power systems. The accuracy and robustness of the impedance-based aggregation are finally validated by simulations and experimental tests.

著录项

获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号