With the wide application of inverter-fed motors (IFMs), it is necessary to monitor the groundwall (GW) insulation status to guarantee the reliable operation of motor drive system. This article first proposes a mathematical model of leakage current in IFM to analyze its time domain characteristics, and then an online GW insulation monitoring method is proposed based on the transient characteristics of leakage current. By using the initial oscillation amplitude, oscillation period, and attenuation time of leakage current, the phase, position, and severity of GW insulation degradation can be identified. The proposed method is validated using an IFM, and the experimental results agree well with theoretical analysis.