1. First, use a psychrometric chart to determine the theoretical minimum temperature (wet bulb) you can get with the cooling tower at your location. In practice, though, the minimum you can achieve is 4—5°F above the wet bulb temperature. (This is called approach.) Because you have high relative humidity of 90 at ambient of 95°F, psychrometric charts show wet bulb close to 95°F. Compare the temperature of cooling water coming out of the cooling tower with the wet bulb temperature. If this temperature is close, your cooling tower is functioning the best it can. However, if the temperature is much higher (say, approach is 10—15°F), you can improve the operation of the cooling tower.
机译:1. 首先,使用湿度图来确定您所在位置的冷却塔可以达到的理论最低温度(湿球)。但是,在实践中,您可以达到的最低温度是比湿球温度高 4-5°F。(这称为方法。由于在 95°F 的环境温度下具有 90% 的高相对湿度,因此湿度图表显示湿球温度接近 95°F。 将冷却塔流出的冷却水温度与湿球温度进行比较。如果该温度接近,则您的冷却塔将发挥最佳性能。但是,如果温度要高得多(例如,接近 10—15°F),则可以改善冷却塔的运行。