Measurement of indoor environmental parameters and analysis of the condensation phenomenon in urban utility tunnels

机译:Measurement of indoor environmental parameters and analysis of the condensation phenomenon in urban utility tunnels

获取原文
获取原文并翻译 | 示例
           

摘要

Condensation is a major issue in the safe operation of utility tunnels. To address the condensation problem, the indoor air temperature, relative humidity (RH) and surface temperature in an urban utility tunnel in Jining were continuously measured, and the condensation conditions were surveyed and analysed. The results indicated that under natural ventilation conditions, the air temperature in the comprehensive cabin varied from 23.4°C to 24.5°C, the RH fluctuated between 86.4% and 95.3%, and the corresponding air dew point temperature (DPT) remained in the range of 22.2°C–22.9°C. The surface temperature of the water supply pipeline ranged from 17.8°C to 18.5°C, which was far lower than the DPT in the tunnel, resulting in serious condensation. A water supply pipeline with an anti-condensation design was developed based on environmental test data. A 25-mm-thick rubber plastic sponge insulation layer was used to thermally insulate the water supply pipeline, preventing further dew condensation. Furthermore, mechanical ventilation had little effect on reducing the RH in the tunnel and may actually cause dew condensation; therefore, a ventilation control mode was proposed in this study. These results are expected to provide basic data for further research and reference for the safe management of utility tunnels.

著录项

获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号