首页> 外文期刊>IEEJ Transactions on Electrical and Electronic Engineering >Ladder‐Wise calculation method for i z/iz ‐coordinate of transformer PD source based on planar layout UHF antenna sensors
【24h】

Ladder‐Wise calculation method for i z/iz ‐coordinate of transformer PD source based on planar layout UHF antenna sensors

机译:基于平面布局UHF天线传感器的变压器PD源i z z-坐标的计算方法

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

In locating a transformer partial discharge (PD) source, there is a large fluctuation error in the z ‐coordinate of the location, which results with planar layout ultrahigh‐frequency (UHF) antenna sensors. For the large fluctuation error, this paper first theoretically analyzes the reason. According to the theoretical analysis results, a ladder‐wise calculation method of the PD source z ‐coordinate is proposed: first, the x ‐ and y ‐coordinates of the PD source are calculated, then the univariate equation f ( z ) is derived, and the z ‐coordinate of the PD source is obtained by f ( z ). Finally, the positioning effect of the ladder‐wise calculation method for PD source z ‐coordinate is verified experimentally. Experimental results show that the proposed method can reduce the fluctuation of the z ‐coordinate of the PD source from 0.6 to 0.2, and when the PD location sample set is ≥10, the average absolute error of the z ‐coordinate is reduced from about 0.4 m to less than 0.1 m. © 2019 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
机译:在定位变压器部分放电(PD)源时,位置的 z - 共协调中存在较大的波动误差,这是由平面布局超高频率(UHF)天线传感器产生的。对于大波动误差,本文理论上首先分析原因。根据理论分析结果,提出了PD源 z - 坐骑的计算方法:首先, x y y 计算PD源的坐标,然后得出Univariate方程 f ( z ),然后pd的 z - 坐标来源是通过 f ( z )获得的。最后,通过实验验证了PD源 z 坐标的梯形计算方法的定位效果。实验结果表明,所提出的方法可以减少PD源的 z z 坐标的波动,从0.6到0.2,当PD位置样本集≥10时, Z - 坐标从约0.4 m减少到小于0.1 m。 ©2019日本电气工程师研究所。由John Wiley&amp出版Sons,Inc。

著录项

获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号