Experimental investigation of solar assisted ground source heat pump system has been carried out to understand performance variation during space heating for continuous eight hours operation from morning to evening for Indian winter climatic conditions. Heat extraction rate from solar collector and ground exchanger were monitored from 9 AM to 5 PM on hourly basis by measuring the inlet and outlet temperatures of heat transfer fluids. A detailed thermodynamic energy balance carried out on hourly basis indicates maximum heat loss is observed at 12 noon at which maximum heat extraction from solar collector and ground heat exchanger was obtained. Maximum COP of the SAGSHP system is observed at 12 noon for all the three mass flow rates, however, the COP decreases up to 3 % with increase in severity of winter due to increase in heat loss. About 44 % increase in mass flow rate of heat carrying fluids has enhanced the heat extraction rate up to 18 %, resulting in about 3 % increase in room temperature. The SAGSHP system was able to maintain the room temperature at about 20 to 21 A degrees C when the ambient temperature was at about 12 degrees C.
机译:对太阳能辅助地源热泵系统进行了实验研究,以了解在印度冬季气候条件下,从早上到晚上连续运行8小时的空间供暖期间的性能变化。通过测量传热流体的入口和出口温度,每小时从上午9点到下午5点监测太阳能集热器和地面换热器的热量提取率。每小时进行的详细热力学能量平衡表明,中午12点观测到最大热损失,此时从太阳能集热器和地下换热器中获得的热量最大。在所有三种质量流量下,SAGSHP系统的最大COP均在中午12点观测到,然而,由于热量损失增加,COP随着冬季严重程度的增加而降低,最高可达3%。载热流体的质量流量增加约44%,使热提取率提高至18%,导致室温增加约3%。当环境温度约为12摄氏度时,SAGSHP系统能够将室温保持在约20至21摄氏度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号