摘要

One of critical issues for HTS transformers is achieving sufficiently low AC loss in the windings. Therefore, accurate prediction of AC loss is critical for the HTS transformer applications. In this work, we present AC loss simulation results employing the H-formulation for a 1 MVA 3-Phase HTS transformer. The high voltage (HV) windings are composed of 24 double pancakes per phase wound with 4 mm - wide YBCO wire. Each double pancake coil has 38 1 / 4 turns. The low voltage (LV) windings are 20 turn single-layer solenoid windings wound with 15/5 (15 strands of 5 mm width) Roebel cable per phase. The numerical method was first verified by comparing the numerical and experimental AC loss results for two coil assemblies composed of two and six double pancake coils (DPCs). The numerical AC loss calculated for the transformer was compared with the measured AC loss as well as the numerical result obtained using the minimum magnetic energy variation (MMEV) method. The numerical AC loss result in this work and experimental result as well as the numerical result using MMEV at the rated current agree to within 20%. Further simulations were carried out to explore the dependence of the AC loss on the gap between the turns of the LV winding. The minimum AC loss at rated current in the 1 MVA HTS transformer appears when the gap between turns is approximately 2.1 mm turn gap in the LV winding. This is due to the change of relative heights between the HV and LV windings which results in optimal radial magnetic field cancellation. The same numerical method can be applied to calculate AC loss in larger rating HTS transformers.
机译:HTS变压器的关键问题之一是在绕组中实现足够低的交流损耗。因此,对AC损耗的精确预测对于HTS变压器应用至关重要。在这项工作中,我们呈现了用于1MVA 3相HTS变压器的H制剂的AC损耗仿真结果。高压(HV)绕组由每相伤口24个双煎饼组成,具有4毫米宽的YBCO线。每个双煎饼线圈都有38个1/4圈。低电压(LV)绕组是20转动单层螺线管绕组缠绕,每相用15/5(15股5mm宽度)滚动电缆。首先通过比较由两个和六个双煎饼线圈(DPC)组成的两个线圈组件的数值和实验AC损耗结果来验证数值方法。将用于变压器计算的数值交流损耗与测量的AC损耗进行比较,以及使用最小磁能变化(MMEV)方法获得的数值结果。数值交流损耗在此工作和实验结果以及使用MMEV的实验结果以及在额定电流中的数值结果同意在20%以内。进行了进一步的模拟,以探讨交流损耗对LV绕组的转弯之间的间隙的依赖性。当匝数之间的间隙约为2.1mm在LV绕组中时,出现1个MVA HTS变压器中的额定电流的最小交流损耗。这是由于HV和LV绕组之间的相对高度的变化导致最佳的径向磁场消除。可以应用相同的数字方法来计算较大额定值HTS变压器中的AC损耗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号